# Operating room pressure alarm response log

> Record an operating room pressure alarm on one job: what tripped, who responded, the checks, the fix, when the room was back in range, and follow-up.

*Markdown mirror of https://hvacsoftware.com/hospital/operating-room-pressure-alarms/.*

An operating room pressure alarm response log is the record of one response on one room. It names what tripped, who responded, what was checked, what was fixed, when the room was confirmed back in the facility's range, and the follow-up work order. The close-out stays on the same job, so the next shift can read it.

A. Ruiz takes the call for OR-2. The charge nurse says the room-pressure alarm is on. The job opens on OR-2 and on AHU-07, the air handler that serves that room, and the notes stay with it.

## What is an operating room pressure alarm response log?

A room-pressure alarm tells the people in the suite that the operating room is outside the pressure relationship the facility set for it. An operating room is kept positive to the corridor and the rooms beside it, so air moves out of the room rather than in. The log is not the alarm. It is what the responding technician writes after someone reports it.

| What the log holds | What a reader can see |
| --- | --- |
| What tripped | The room, and how the alarm was reported |
| Who responded | The technician on the job |
| What was checked | Doors, airflow, filters, dampers and the fan |
| What was fixed | The work done on that visit |
| Confirmed back in range | When the room matched the facility's own range |
| Follow-up | The next work order, on the same air handler |

The [CDC's environmental infection-control recommendations](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html) say an operating room keeps positive-pressure ventilation with respect to corridors and adjacent areas, and that the doors stay closed except for equipment, personnel and patients. [CDC's air guidance](https://www.cdc.gov/infection-control/hcp/environmental-control/air.html) describes positive pressure as air that flows away from the room toward the adjacent space. The setpoints and the air-change rates belong to the facility's infection-control program and its engineering standard.

Those lines are the facility's expectations of the room. The contractor's log has to be complete enough that infection control and engineering can read what was found and what was left. It does not replace their standard.

## What should each pressure alarm response record include?

Each record is the work of that response, written so a person who was not in the room can read it. For OR-2, the line is the pressure alarm, the responder is A. Ruiz, and the air handler is AHU-07. Write only the room this visit is for.

| On the record | What to write | What to leave off |
| --- | --- | --- |
| What tripped | OR-2, room-pressure alarm, reported by the charge nurse | A cause nobody confirmed |
| Who responded | A. Ruiz | A name that was not on the job |
| Checks | Doors, airflow, filters, dampers and the fan | A step nobody performed |
| What was fixed | The damper that was reset, the door that would not close | Work that is still open |
| Confirmed | Back in the range the facility uses, and when | A pressure number you did not read |
| Follow-up | The filter change, as its own job on AHU-07 | A note that lives only in a truck folder |

Write the checks and the findings that belong to that visit. When the work changed a filter, a damper or a door closer, those notes sit on the same job. A [commercial work order](https://hvacsoftware.com/work-orders/commercial/) keeps the site, the room and the close-out together, and [asset records](https://hvacsoftware.com/assets/equipment-records/) keep the air handler's history.

## What does the responding technician check?

The check is physical, and it starts with the room. A door held open can drop the room's relationship to the corridor. The technician looks before writing that the room is back in range.

1. Doors. Confirm the operating room doors are closed, including a door that was propped for a case.
2. Airflow. Confirm the supply and return grilles are clear, and that air is moving the way the facility's balance says it should.
3. Filters. Look at the filters on the air handler that serves the room, and note when they are loaded.
4. Dampers and the fan. Confirm the fan is running and write where the damper that serves the room was found, or what you reset.
5. The room. Confirm the pressure relationship against the range the facility posted for that room, and write that it was confirmed.

One hospital's perioperative workflow for a pressure loss tells staff to confirm the doors are closed and the supply and return grilles are unobstructed, then to call maintenance and infection control if the condition remains ([UNC Medical Center staff workflow](https://spice.unc.edu/wp-content/uploads/2024/06/UNC-Medical-Center-Staff-Workflow-Temp-Humidity.pdf)). That form is one facility's procedure. The hospital's own infection-control program is the one the technician follows.

## Who raises the alarm, and who keeps the response log?

The facility's own room-pressure system raises the condition. HVAC Software does not receive that alarm, and it does not control the fan, the damper or the setpoint. A person reports the room, and a person opens the job.

- **The building system.** It raises the condition and keeps the trend the engineers read.
- **The request.** A phone call or a facilities request opens the job. The alarm itself does not.
- **The technician.** The checks, the fix and the confirmation are written on that job.
- **The facility.** Infection control and engineering keep the standard and decide when the room can be used.

The [CDC recommendations](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html) also say to take immediate steps to restore fixed ventilation for an operating room, and to keep backup ventilation equipment for that room until the fixed system is back. [ASHE's note on operating-room airflow](https://www.ashe.org/system/files/media/file/2022/04/12-Evaluate-and-Implement-OR-Airflow-Setback.pdf) is guidance a facility uses when it looks at that airflow. The range on the alarm is the one the facility adopted. [Cooling maintenance records](https://hvacsoftware.com/data-center/maintenance-records/) are the same idea on a cooling unit: one visit, with the close-out on the job.

## How should the response and the follow-up sit on one job?

The response belongs on the room and on the air handler, not in a folder that left on the truck. OR-2 holds the pressure response. AHU-07 holds that visit and the filter change that follows it.

1. Open the job on the room that alarmed, and name the air handler that serves it.
2. Write what was reported, who responded, and the checks from that visit.
3. Write what was fixed, and when the room was confirmed back in the facility's range.
4. Open the follow-up as its own job on the same air handler. When that visit is planned work, it comes from the service agreement.
5. Close the response on the same record the call opened.

A PM visit generated from a [service agreement](https://hvacsoftware.com/preventive-maintenance/service-agreements/) is still a job on that air handler. The person who sends the technician uses [dispatch](https://hvacsoftware.com/dispatch/), and the follow-up window is set in [scheduling](https://hvacsoftware.com/scheduling/). The history stays in one place, from the first call to the paid invoice.

## How does HVAC Software help a contractor keep the response log?

Residential and commercial work run in one system. The visit, the work order and the invoice sit on one record from the first call to the paid invoice.

- **The record.** One record from the first call to the paid invoice, for a house or a commercial building.
- **The agreement.** PM visits come from the service agreement and stay on the air handler.
- **The phone.** The technician's jobs and schedule show on their phone.

See the response on the room it belongs to. [Book a demo](https://calendly.com/jeel-fieldcamp/30min?utm_source=hvacsoftware&utm_medium=article&utm_content=aio&utm_campaign=hospital-or-pressure-alarms) and walk one pressure alarm from the call to the follow-up job.

The response stays on the room in [hospital maintenance](https://hvacsoftware.com/hospital/).

## Questions

### What belongs on an operating room pressure alarm response log?

The log names what tripped, who responded, the checks, what was fixed, when the room was confirmed back in the facility's range, and the follow-up work order. Keep that on the job for the room and the air handler that serves it. A pressure number you did not read does not belong on the line.

### Does this software receive the room-pressure alarm from the building system?

No. The facility's own room-pressure system raises the alarm. HVAC Software does not receive that alarm, and it does not control the fan, the damper or a setpoint. The record starts when a person calls or a facilities person opens the job.

### What should a technician check before writing that the room is back in range?

Check the doors, the supply and return path, the filters, and the dampers and fan on the air handler that serves the room. Then confirm the room against the range the facility uses for that operating room. Write only the checks that were done.

### Where does the follow-up work order live?

On the air handler that serves the room, as its own job. A planned filter change or a later PM visit comes from the service agreement and stays on that unit. The response job keeps the link, and the follow-up keeps its own close-out.

### Does the response log replace the hospital's infection-control standard?

No. The facility's infection-control program and its engineering standard set the pressure relationship and when the room can be used. The contractor's job is the record of the response. That standard is what the room is held to.